86 First commissioning and modifying network settingsInstallation and Operating Instructions CGLine+ Web-Controller 40071860236 (E) February 2019 www.eaton.comResistor must be connected next to the switch.S1 CGLineS2 InterfaceOption inputs (In1/In2):Programmable digital inputs. The inputs are activated bybridging of both contacts of In1 or In2.The following functions can be freely assigned to the digitalinputs:n Rest ordern Maintained Light ON/OFF per Linen Start function testn Stop testn External failureRelay outputs:The CGLine+ Web-Controller also has 2 freely programmablerelay outputs each with a change-over contact.Programmable functions:n At least one luminaire failuren Three consecutive luminaire failuren Communication failuren Battery operationn Function test activen Duration test activen Charging failuren Test failureAssignment:Relay 1: Relay 2:212224111214USB connections:The CGLine+ Web-Controller has 2 USB connections: 1 x USB Ahost and 1 x USB B device.USB1 (Type A host):A standard USB storage stick can be connected to this USBport to save the current configuration and the logbook to theUSB stick.USB2 (Type B device):This USB connection enables connection of the CGLine+Web-Controller to a standard PC. Controller functions can beprogrammed via the PC and a configuration software, e.g.luminaire configurations. The PC configuration software isavailable optionally.6 First commissioning and modifyingnetwork settingsThe network settings of the Web-Controller can be modifiedby the CGLine+ PC software or via web browser. The followingprocedure describes the setup via web browser.NOTEFor correct perform of the duration test and function test thedate and the time must be adjusted (see chapter 6.5).6 1 Factory default nework settingsThe CGLine+ Web-Controller is supplied as standard with thefixed IP address 192.168.1.200. Operation via DHCP (dynamicIP address assignment) is possible but not factory-activated.Because typical company networks only permit own-assignedIP addresses, we recommend configuring network settings viadirect connection to a PC, e.g. a notebook.6 2 Preparing the PC for configurationIt is mandatory to observe the following:n For direct connection from the CGLine+ Web-Controller toa PC, a crossover cable is required.n The devices must be in the same subnet, meaning the net-work card of the PC must be set to 192.168.1.xxx (not equalto 200), e.g. 192.168.1.50 (subnet to 255.255.255.0).n Settings for gateway and DNS must not be taken intoaccount with a direct connection.Connection example for direct connection:PC network setting:To modify the network settings of the PC open the systemcontrol Network and release centre