75 InstallationInstallation and Operating Instructions CGLine+ Web-Controller 40071860236 (E) February 2019 www.eaton.comSystem button 3The system button enables the CGLine+ Web-Controller to beconnected to a PC. If pressed for ~ 3 seconds, the green USB2LED turns on and an external storage from Windows will bedetected. An access via PC software will be possible now. Toremove the controller the following steps are required:1. Remove external hard drive via windows2. Press system button for 3 seconds, green USB2 LED willturn offFig 3 Connecting the controller to a laptop with CGLine+PC-Software via USB A-BReset button 3The reset button resets the CGLine+ Web-Controller (not fac-tory default). For this purpose, the button must be pressedand held for >1 second.5 2 3 Connections230 V/AC 6Connection terminals for power supply 230 V/ AC with 50/60Hz.CGLine+ Bus: 7The Web-Controller is compatible to the old CGLine technlogy.If one or more CGLine luminaires are connected, the CGLinecompatible mode is active. Following luminaires can be con-nected:Table 2. Max. number of luminaires to be connectedLine No. CGLine CGLine+4 lines 2 lines1 100 200 4002 100 200 4003 100 200 -4 100 200 -Total 400 800 800Polarity D1/D2 to the luminaires must not be observed. Cablerouting for CGLine bus: 2-core bus line, unshielded, free bustopology possible.Table 3 Cable length/lineCross-section Length Total lines0.5 qmm 260 m 660 m1.0 qmm 520 m 1320 m1.5 qmm 800 m 2000 mTable 4. Electrical data/linePower supply bus 25 VMax. permissible voltage drop 6 VBus current 300 mANOTEIn case of a communication failure with a luminaire pleasecheck the following:1. Check the proper connection of the bus line at the lumi-naire’s connector2. Check the correct bus voltage at the luminaire (see table 4.)3. In case the voltage is correct and the communication failurestill exists: Check the bus line resistance which shouldn’texceed 32 Ohm. For that please disconnect the relevant linefrom the web-controller, apply a short cut between the buscontacts at the affected luminaire and measure the resis-tance at the other end of the line.RS485 8No function. Only for french market.LAN connection 9Ethernet connection via RJ45 socket. A LAN patch cable mustbe used for direct connection of a PC/notebook.Blocking input (S1/S2):All connected luminaires can be blocked via the blockinginput, meaning the luminaires are switched off and the emer-gency light function deactivated, for example for idle operat-ing times.Connection is via a key switch or relay (e.g. alarm system). Toguarantee reliable operation from short-circuit or interruptionof the blocking line, this input is equipped with differentialloop monitoring (static current), meaning a 1kOhm resistancemust be integrated for blocking that defines the static current.Connection example:With closer contactS1 CGLineS2 InterfaceWith opener contact