30Appendix 1Technical parameters and specificationsRemark:① EDX 60-80kVA ≥ 0.99 at full load.② -20%~+10% default; -24%~+15% regulate.③ ECO mode is supported by EDX 60KVA-80KVA in single and parallel machine mode.Model EDX 60KVA EDX 80KVAPower Rating 60KVA/48KW 80KVA/64KWInputConnection 3-Phase + N+GFrequency 40-70HzPower factor ≥0.99 ①Utility voltagerange400×(-48%~ +20%)VAC(when input voltage<72%, output power derating isrequired)Bypass Voltagerange 400×(-24%~ +15%)VAC ②OutputVoltage rating Line voltage 400×(1±1%)VAC or phase voltage 230×(1±1%)VAC(withbalanced load)Power factor 0.8Frequencytolerance50Hz±8%(track bypass frequency input ;when input frequency exceeds ±8% orunder the mode of battery power supply, frequency output should be±0.1%ofnominal)Overload time ≥10min 110%≥1min 125%EfficiencyDouble-conversion mode Up to 94%ECO mode Up to 98% ③OperatingEnvironmentAmbienttemperature 0~40℃Storagetemperature –25~55℃ (without battery)Ambient humidity 0-95%Altitude ≤1000mNominalbatteryvoltage/Ratedchargingvoltage28 Pcs ±168VDC/±189VDC30 Pcs ±180VDC/±202.5VDC32 Pcs ±192VDC/±216VDCWeightN.W/Containtransformer 282Kg 306KgG.W/Containtransformer 356Kg 380KgUPS Dimension(W*D*H)(mm) 600×800×1900 600×800×1900SafetyStandardNationalStandard GB4943TCL certification YD/T1095EMSESD GB/T 17626.2 Level 4RS GB/T 17626.3 Level 3EFT GB/T 17626.4 Level 4SURGE GB/T 17626.5 Level 4EMIRadiation andConduction GB 7260.2WARNING: This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances.