O & M Manual IM05805023KJockey Pump Controllerswww.chfire.comPage 10 EATON CORPORATION4.1.3 DECIMAL POINT: (1000)While holding the PGM button, press the UP Arrow button.The display will show “dp”Release the PGM buttonThe display will show “1000”Do not change the setting.4.1.4 OFFSET Minimum Transducer Pressure: (0 psi)While holding the PGM button, press the UP Arrow button.The display will show “OF”Release the PGM buttonThe display will show “+0000” – note: the “+” flashesDo not change the setting.4.1.5 FULL SCALE VALUE Maximum Transducer Pressure: (500 psi)While holding the PGM button, press the UP Arrow button.The display will show “FS”Release the UP Arrow and PGM buttonsThe display will show “+0500” – note: the “+” flashesDo not change the setting.4.1.6 RELAY 1 – Hi ALARM SETPOINT: (+9999)While holding the PGM button, press the UP Arrow button.The display will show “1Hi”Release the UP Arrow and PGM buttonsThe display will show “+9999”Do not change the setting.4.1.7 RELAY 1 – Lo ALARM SETPOINT: (+0000) Pressure Start PointWhile holding the PGM button, press the UP Arrow button.The display will show “1Lo”Release the UP Arrow and PGM buttonsThe display will show “+0000”Push the RIGHT Arrow button to move the value setting positionSet the desired START Point value using the UP and Down Arrow buttons(eg: For 100psi, the display will show “+0100”)4.1.8 RELAY 2 – Hi ALARM SETPOINTWhile holding the PGM button, press the UP Arrow button.The display will show “2Hi”Release the UP Arrow and PGM buttonsThe display will show “+9999”Do not change the setting.PGM +dp1000+0000+0500+0000+9999EATON XTJP / XTJYPGM +PGM +PGM +PGM +OFFS1Lo1HiEffective: June 2012PGM +2Hi+9999