O & M Manual IM05805023K EATON XTJP / XTJYEffective: June 2012 Jockey Pump ControllersEATON CORPORATION www.chfire.com Page 94. Digital DisplayThe XTJP and XTJY Jockey Pump Controllers are supplied standard with adigital panel meter that indicates the current pressure and Stop and Startpressure set points.LED DisplayHigh Visibility Red Superbright LEDFour full digits0.56in (14mm) high charactersFlashing AlarmsRatingsNEMA 4X1/8 DIN4.1 ProgrammingEnsure the Rotary Disconnect switch and the Hand-Off-Auto selector switchare in the OFF position.Apply power to the Jockey Pump Controller.Once power is applied, turn the Rotary Disconnect switch to the ON position.NOTE: The instructions below are based on the factory default settings.Displayed values may vary depending on the programmed parameter setpointvalues. Factory default settings for each parameter are listed in Table 1.4.1.1 Intial SetupThe Digital Display will show the current system pressure.Press and hold the PGM button.The display will show “run”4.1.2 INPUT: (4.20)While holding the PGM button, press the UP Arrow button.The display will show “inP”Release the PGM buttonThe display is factory set to “4.20”.If the display does not show “4.20”, push the RIGHT Arrow button until “4.20” isdisplayedCurrent System Pressure