O & M Manual IM05805023K EATON XTJP / XTJYEffective: June 2012 Jockey Pump ControllersEATON CORPORATION www.chfire.com Page 3INSTALLATION & MAINTENANCE MANUAL FORJOCKEY PUMP CONTROLLERSIn order to familiarize yourself with the Jockey PumpController, please read the instruction manual thoroughlyand carefully. Retain the manual for future reference.1. Installation and Mounting of the ControllerCarefully unpack the controller and inspect thoroughly.It is recommended that the controller is located as close asis practical to the motor it controlsThe controller is not free standing and must be boltedsecurely to a wall. For dimensional and weight data pleaserefer to the respective data sheets for the Jockey PumpController.2. System Pressure ConnectionThe Jockey Pump Controller is equipped with a PressureTransducer. The controller is provided with a ¼" NPTfemale system pressure connection located on the bottom,external side of the enclosure. The connection should beinstalled as per NFPA, pamphlet No. 20.NOTE: Water lines to the pressure transducer must be freefrom dirt and contamination.The pressure should not exceed what the pressuretransducer is rated for.3. Electrical ConnectionsAll electrical connections should meet national and localelectrical codes and standards.The controller should be located or so protected that theywill not be damaged by water escaping from pumps orpump connections. Current carrying parts of controllersshall be a minimum of 12 inches (305 mm) above the floorlevel.Prior to starting verify all data on the nameplate such as,catalog number, AC line voltage and horsepower.Inspect all electrical connections, components and wiringfor any visible damage and correct as necessary. Ensurethat all electrical connections are tightened beforeenergization.Install necessary conduit using proper methods and tools.Incoming AC line voltage is clearly marked L1, L2, L3 andground, located at the top of the breaker.