164201535---2 1 of 2PHYSICAL FEATURES AND REQUIREMENTS081505CDESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:Installation InformationA-3EATON Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev E powerware.com1. The UPS equipment operating environment must meet the weight requirements shown inTable A and the size requirements shown on Drawing 164201535 ---9.2. The UPS cabinet is palleted separately for shipping.3. Do not tilt cabinets more than 10˚ during handling.4. Dimensions are in millimeters (inches).5. The cabinet can be installed in line-up-and-match or standalone configurations.Table A. UPS Cabinet WeightModel Voltage Weightkg (lb)Input Output Shipping Installed Point LoadingPowerware 9390---40/40 208V/220V 208V/220V 263 (580) 241 (530) 4 at 60.3 (133)Powerware 9390---40/40 480V 480V 231 (508) 208 (458) 4 at 52.2 (115)Powerware 9390---80/40 208V/220V 208V/220V 313 (690) 290 (640) 4 at 72.5 (160)Powerware 9390---80/40 480V 480V 271 (618) 258 (568) 4 at 64.5 (142)Powerware 9390---80/50 208V/220V 208V/220V 313 (690) 290 (640) 4 at 72.5 (160)Powerware 9390---80/50 480V 480V 271 (618) 258 (568) 4 at 64.5 (142)Powerware 9390---80/60 208V/220V 208V/220V 313 (690) 290 (640) 4 at 72.5 (160)Powerware 9390---80/60 480V 480V 271 (618 258 (568) 4 at 64.5 (142)Powerware 9390---80/80 208V/220V 208V/220V 313 (690) 290 (640) 4 at 72.5 (160)Powerware 9390---80/80 480V 480V 271 (618 258 (568) 4 at 64.5 (142)6. The clearances required around the UPS cabinet are shown in Table B .Table B. UPS Cabinet ClearancesFrom Top of Cabinet Minimum clearance over the UPS cabinet is457.2 mm (18 inches) for ventilationFrom Front of Cabinet 914.4 mm (36 inches) working spaceFrom Back of Cabinet None requiredFrom Right Side of Cabinet None requiredFrom Left Side of Cabinet None required