POWER WIRING INSTALLATION NOTES032406D164201535---5 2 of 17DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:Installation InformationA-12 EATON Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev E powerware.comTable F. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390---80/50Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pF load kVAkW50455045Input and Bypass InputOutputVOLTSVOLTS208/220208/220480480AC Input to UPS Rectifier (0.98 min. pF)Full Load Current plus Battery Recharge Current(3) Phases, (1) Ground AAmps 155 67Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)4/0(1)2(1)AC Input to UPS BypassFull Load Current(3) Phases, (1) Neutral---if required, (1) Ground BAmps 139/131 60Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)4/0(1)2(1)DC Input from Battery to UPS(1) Positive, (1) NegativeCVdcAmps@ (2.0V/cell)384---480126432---480126Minimum Conductor SizeNumber per PoleAWG or kcmil(each)1/0(1)1/0(1)AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral---if required, (1) Ground D Amps 139/131 60Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)4/0(1)2(1)Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 7) --- AWG or kcmil(each)2(1)6(1)NOTE: Callout letters A, B, C, and D map to Drawing 164201535 ---4, sheets 1 of 5,3 of 5, 4 of 5, and 5 of 5.6. The bypass feed into this equipment uses three or four wires. The rectifier feed into thisequipment uses three wires. The phases must be symmetrical about ground (from a Wyesource) for proper equipment operation.7. If the load requires a neutral, a bypass source neutral must be provided. If the load doesnot require a neutral and there is no neutral conductor connected at the bypass input, aneutral to ground bonding jumper must be installed. DO NOT install both a source neutraland a bonding jumper. See Table E through Table H for neutral bonding jumper wire sizes.Bonding jumper must be copper wire.C A U T I O NHIGH IMPEDANCE GROUND SOURCES - If the source of supply is a high impedance ground (IT)type, the input neutral conductor must be connected from the source of supply. If there is nooutput neutral connected to the UPS, the neutral-forming transformer kit (PN 103005400) maybe used instead of pulling a neutral from the source. If the load requires a neutral then aninput neutral conductor must be pulled into the UPS. In no circumstances shall a neutral toground bonding jumper be installed in the UPS.