POWER WIRING INSTALLATION NOTES081505C164201535---5 9 of 17DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:Installation InformationA-19EATON Powerware® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev E powerware.com14. External overcurrent protection is not provided by this product, but is required by codes.Refer to Table E through Table H for wiring requirements. If an output lockable disconnectis required, it is to be supplied by the user.15. Table L lists the maximum rating for input circuit breakers. When wiring a single-feed input,the rating requirements for the input circuit breakers are superceded by the ratings listed inTable M.Table L. Maximum Input Circuit Breaker RatingsUPS Model Input Voltage Rating208V/220V 480VPowerware 9390---40/40Powerware 9390---80/4080% Rated 175A 70A100% Rated 150A 60APowerware 9390---80/50 80% Rated 225A 100A100% Rated 175A 80APowerware 9390---80/60 80% Rated 250A 125A100% Rated 200A 90APowerware 9390---80/80 80% Rated 350A 150A100% Rated 300A 125AC A U T I O NTo reduce the risk of fire, connect only to a circuit provided with maximum inputcircuit breaker current ratings from Table L in accordance with the National Electricalcode, ANSI/NFPA 70.16. Source protection for the AC input to bypass should be treated as if supplying an 80 kVAthree-phase transformer, to allow for inrush current if an IDC with a transformer is installed.Bypass input wiring and bypass input breaker rating should be treated as if supplying an80 kVA load, regardless of the rating of the UPS.17. The line-to-line unbalanced output capability of the UPS is limited only by the full loadper phase current values for AC output to critical load shown in Table E through Table H.The recommended line-to-line load unbalance is 50% or less.