S811+ Operating Configuration32 S811+ Soft Starter MN03900001E—November 2012Initial Configuration:1. It is suggested that the S811+ Soft Starter be configuredbefore applying the line voltage. Before applying the Linevoltage, apply 24 Vdc to the Supply connections of theS811+’s control terminal block.2. Set the Operating Parameters to the desired values.These settings assume the motor has a 1.15 ServiceFactor.Operating Parameters—Soft Start Configuration—S811+ …N3S StandardSoft Start Config Menu UnitsMinimumInline(InsideDelta)MaximumInline(InsideDelta)DefaultInline(InsideDelta) NotesAccessLevelMtr Nameplate FLA 2S811+N37… Amps 11 (19) 37 (65) 11 (19) Motor FLA parameter must be set to motornameplate FLA to achieve proper overloadprotection.2S811+N66… Amps 20 (35) 66 (114) 20 (35) 2S811+R10… Amps 32 (55) 105 (182) 32 (55) 2S811+R13… Amps 42 (73) 135 (234) 42 (73) 2S811+T18… Amps 56 (97) 180 (311) 56 (97) 2S811+T24… Amps 75 (130) 240 (415) 75 (130) 2S811+T30… Amps 95 (164) 304 (526) 95 (164) 2S811+U36… Amps 112 (195) 360 (623) 112 (195) 2S811+U42… Amps 131 (227) 420 (727) 131 (227) 2S811+U50… Amps 156 (270) 500 (865) 156 (270) 2S811+V36… Amps 112 (195) 360 (623) 112 (195) 2S811+V42… Amps 131 (227) 420 (727) 131 (227) 2S811+V50… Amps 156 (270) 500 (865) 156 (270) 2S811+V65… Amps 203 (352) 650 (1125) 203 (352) 2S811+V72… Amps 225 (389) 720 (1246) 225 (389) 2S811+V85… Amps 265 (458) 850 (1471) 265 (458) 2S811+V10… Amps 312 (539) 1000 (1732) 312 (539) 2Ovrld Trip Class 5 30 20 2Phase Rev Fault 0 1 0 0 = Enabled1 = Disabled2Phase Sequence 0 1 0 0 = ABC1 = ACB2Start Method 0 1 0 0 = Voltage Ramp1 = Current Limit2Initial Torque % 0 85 45 1Soft Start Time Seconds 0.5 180 20 1Kick Start Torq % 0 85 0 1Kick Start Time Seconds 0 2 0 1Soft Stop Time Seconds 0 60 0 1Reset Mode 0 2 0 0 = Manual1 = Auto2 = Powerup Reset2Auto Reset Delay Seconds 0.1 600 0.1 2Auto Reset Limit 0 10000 0 2Motor Wiring Config 0 1 0 0 = Inline1 = InsideDelta2