Appendix G—Modbus Register Map70 S811+ Soft Starter MN03900001E—November 2012Motor Start Method 1 608 R/W UINT8 0 = Voltage Ramp1 = Current Limit2 = Unavailable3 = Pump Start (w pump option)Percent Initial Torque 1 609 R/W UINT8 0–100%Motor Start Ramp Time 2 610 R/W UINT16 0.5–180s (in 0.1 sec)Motor Stop Ramp Time 2 611 R/W UINT16 0.0–60.0s (in 0.1 sec)Motor Pump Stop Time 2 612 R/W UINT16 20.0–120.0 (in 0.1 sec)Kick Start Initial Torque 1 613 R/W UINT8 0–100%Kick Start Time 1 614 R/W UINT8 0.0–2.0 sec (in 0.1 sec)Ramp2 Motor Phase Sequence 1 615 R/W UINT8 0 = ABC Phase sequence1 = ACB Phase sequenceRamp2 Motor Start Method 1 616 R/W UINT8 0 = Voltage Ramp1 = Current Limit2 = Unavailable3 = Pump Start (w pump option)Ramp2 Motor Percent InitialTorque1 617 R/W UINT8 0–100%Ramp2 Motor Start Ramp Time 2 618 R/W UINT16 0.5–180s (in 0.1 sec)Ramp2 Motor Stop Ramp Time 2 619 R/W UINT16 0.0–60.0s (in 0.1 sec)Ramp2 Motor Pump Stop Time 2 620 R/W UINT16 20.0–120.0 (in 0.1 sec)Ramp2 Motor Kick Start InitialTorque1 621 R/W UINT8 0–100%Ramp2 Motor Kick Start Time 1 622 R/W UINT8 0.0–2.0 sec (in 0.1 sec)Motor Control Terminal BlockLocal Control Enable1 623 R/W UINT8 1 = local control only enabled0 = disable(terminal block input selects local/networkcontrol)Motor Control Input ConfigurationS811 input#1 cfgS811 input#2 cfgS811 input#3 cfgS811 input#4 cfgNetwork input#1 cfgNetwork input#2 cfgNetwork input#3 cfgNetwork input#4 cfg22222222624625626627628629630631RWRWRWRWRWRWRWRWUINT16UINT16UINT16UINT16UINT16UINT16UINT16UINT160 = No function1 = Run12 = Ramp23 = Jog4 = Local control enable5 = Fault reset6 = E-stop input7 = Alarm-No-Trip8 = External Trip9 = External Warning10 = Disable overload on start11 = Analog Input (S811 input #4 only)Analog Input Data Range 1 632 R/W UINT8 Value0x010x020x03Descriptionnot supported0–20 mA range4–20 mA rangeRegister Map, continuedParameterDataLengthModbusRegisterNumber Read/WriteDataType Description