System OperationCopyright © 2008-2011 Eaton Corporation. All Rights Reserved.IPN 997-00012-63C August 2011 17► To enable Battery Test (or to start or stop a test manually) Use the SC100 keypad to go to: Menu > Configuration > Battery Test > Edit. Or, in DCTools go to: Control Processes > Battery Test► To use an external relay contact to activate a Battery Test (optional) Connect a voltage free relay contact or switch to any Digital Input. In DCTools go to Digital Inputs. Configure the selected Digital Input and set Function to Start Battery Test.► To reset a Battery Test Fail alarm In DCTools go to: Alarms. Click on Reset Battery Test Fail.InformationThe following information is available about Battery Test.Parameter Description Where to find:State Indicates if Battery Test is disabled, locked-out, activeor inactive. SC100*: Menu > Controls >Battery TestDCTools: Control Processes> Battery TestRemaining Time The time to the end of the currently active Battery Test.Next Start Time The time to the start of the next Battery Test.Lockout Remaining The time remaining until a Battery Test can be started.DCTools: Control Processes> Battery TestVoltage Offset The adjustment to the bus voltage being applied due tothe Battery Test. While a Battery Test is running, therectifiers are turned down to force the battery to carrythe load.*Only if Battery Test is Enabled.ConfigurationSet the following parameters.Parameter Description Where to find:TerminationVoltageIf the bus voltages drops below this value during aBattery Test, then the test fails. SC100: Menu >Configuration > Battery TestDCTools: Control Processes> Battery TestDuration The maximum time a Battery Test process will beactive. The battery test will pass if the bus voltageremains above the Battery Test Termination Voltagefor the duration of the test.Interval The time between scheduled battery tests. The intervalperiod begins at the start of a battery test. Zero disablesscheduled battery tests. Zero also disables the Lockoutfollowing an ac supply failure, allowing an immediatemanual test. DCTools: Control Processes> Battery TestLockout Battery Test is is not able to start for this period afteran ac fail. This allows time for a battery to rechargebefore a Battery Test.