Sonix Vw2 Technical Manual10 SONIX VW2 TECHNICAL MANUAL TM368 / A May 2022 www.eaton.com4.7 Beacon output connectionThere are two independent Beacon output portsavailable on each Sonix Vw2 unit; both divided intoOutput and Return terminals.The Output terminals are the primary terminals and theReturn are optionally used to connect the return side ofa loop.Maximum cable section supported by the output portsare:Solid: 16.0 mm 2Stranded: 16.0 mm 2 including sleeved or non-sleeved ferruleWarning: Possible hazardous voltages present.Great care should be taken during installation andmaintenance of this unit. Cover should not beremoved during live operation. The cover needsto be replaced after installation or maintenanceof the unit.4.7.1 Maximum load and fusingThe maximum load that can be connected to a singleVw2 output port is based on 2 parameters; surgecurrent and steady state current.The maximum allowable steady state current is limitedto 10 A by the internal fuse but can be reduced if alower value RCBO is installed in the beacon supply.The maximum allowable peak surge current is limited to100 A by the on-board relays.The unit is fitted with a pair of 10 A 10 x 38 mm Mersenfuses, part number S218194.Warning: Only replace fuses with originalmanufacturer or equivalent.Warning: Beacons without soft-start circuits canhave peak surge currents of 100x steady statecurrent.4.7.2 Connecting beacons as a loopThe Sonix Vw2 unit has been designed to allow for idleloop health monitoring by energizing the loop for a shortperiod of time, not enough to activate the attachedbeacons, but enough to detect a healthy loop.The Earth terminals that are part of the Vw2 outputare provided for functional earthing only, Protectiveearth connections should be terminated directly to theprotective earth.Figure 7 - Typical beacon loop wiring4.7.3 Connections as a spurThe field beacon units can be connected as spur, ratherthan a loop.Figure 8 - Spur wiringote:N Loop monitoring is not available if beacons are wired as a spur.Vw2 UnitSonix PA/GAL / +N / -ERETURNL / +N / -EOUTVw2 UnitSonix PA/GAL / +N / -ERETURNL / +N / -EOUTJ1J2F2F1J6J5J3D20J4Beacon SupplyPrimary L / +N / -EJ2RelayOther Vw2 unitsTTBeacon SupplyPrimaryBeacon SupplySecondaryBeacon SupplyPrimaryBeacon SupplyL / +N / -EJ2TTL / +N / -EL / +N / -EJ1 / J6