Tripp Lite by Eaton SmartPro Advanced User Guide 614-40195—Rev 01 433000 > 85%Frequency regulation +/-0.1 HzNominal output 200/208/220/230/240V100/110/120/125VtFrequency Follows input frequency 50/60HzOutput overload [105%,120%] 30min[120%,150%] 5min>150% 10s[105% ~110%] 10s[110% ~150%] 1s,>150% 0.15sShort circuit current limitation inbattery modeModel Current limitation1500 38A3000 64ATransfer time Utility Outage: 1-4ms for normal mode, >5ms for sensitive modeUtility abnormal: <10ms for normal mode ,<25ms for sensitive mode88..77 EElleeccttrriiccaall OOuuttppuutt CCoonnnneeccttiioonnCatalog Number Output connection Output cableSMX1500XLRT2USMX1500XLRT2UN(4) IEC10A Primary group(2) IEC10A Group 1(2) IEC10A Group 2(2) IEC10ASMX3000XLRT2UASMX3000XLRT2UN(4) IEC10A + (1) IEC16A Primary group(2) IEC10A + (1) IEC16A Group 1(2) IEC10A Group 288..88 BBaatttteerryyInternal batteries EBMSpecifications 1500VA: 48Vdc - 4 x 12V, 9Ah3000VA: 72Vdc - 6 x 12V, 9AhBP48VRM2U: 48Vdc - 2 x 4 x 12V, 2 x9AhBP72VRM2U: 72Vdc - 2 x 6 x 12V, 2 x9AhType Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-5 year floatservice life at 25°C (77°F).Monitoring Advanced monitoring for earlier failure detection and warningEBM battery cable length 2U EBM cable length:350mm/13.78inSpecification and Technical Characteristics