3. Installation3.1 Prerequisites for the location of use3.1.1.3 Criteria for the installation positionThe XV300 are intended to be flush mounted in control cabinets, control panels, or con-trol consoles.l XV300 units can be installed in landscape or portrait mode.If you are using your XV300 unit with an SD card, do not install it with the SD slotfacing downwards, as the SD card may fall out otherwise.l If no forced ventilation is being used, the device must not be mounted at an angle ⍺of more than ±α ≦ 45° relative to its fully vertical position.l The enclosure material must be thick enoughFor front mounting: 2 mm (0.08") ≦ d ≦ 5 mm (0.2"),For rear (panel) mounting: d = 1.5 mm (0.059") ± 0.1mm (0.004")Flatness ≦ 0.5 mm (0.02") at the mounting cutout with Rz ≦ 120; IP 65 → DINISO 2768-2 (K)l Recommended mounting cutoutFor front mounting:XV-303-70-..:e = 183mm (7.20") ± 1mm (0.04"), f=122mm (4.80") ± 1mm (0.04")XV-303-10-..: e = 255.5mm (10.06") ± 1mm (0.04"), f = 160.5mm (6.32") ± 1mm (0.04"),For rear (panel) mounting:XV-313-70-..: e = 182.7mm (7.193") ± 0.1mm (0.004"), f = 126.8mm (4.992") ± 0.1mm(0.004")XV-313-10-..: e = 255.7mm (10.07") ± 0.1mm (0.004"), f = 165.8mm (6.528") ± 0.1mm(0.004")Figure 14: Mounting positionXV300 12/15 MN048017 EN www.eaton.eu 33