9XSTORAGE HOME POWER METERS MANUAL MN700001EN March 2019 www.eaton.com/xstorageFigure 17: SFERE power meter wiring terminalsThe hybrid inverter RS-485 port terminals are located in thecommunication slot that is highlighted by the arrow pointer inFigure 18. Please note that up to two devices (in this case, twopower meters) can be connected through the hybrid inverter’sRS-485 port.Figure 18: Connection of the RS845 terminal blockconnector to the RS-485 port of the hybrid inverterThe wiring of the RS-485 port terminals of the hybrid inverterand the power meters terminals is illustrated in Figure 19:• Connect the RS-485 terminals of the power meter tothe RS-485 terminal block using a 1 mm2 cable, whichis included in the accessory box kit provided with thexStorage Home system and described in the xStorage Homeinstallation manual;• The connection to the RS-485 connection port of the hybridinverter should be realized via the RS-485 terminal block.Figure 19: Wiring the hybrid inverter and the power metersvia the RS-485 portFigure 20: RS-485 connector terminalsThe design of the RS-486 connector terminals is illustrated inFigure 20. PreviousNext |