www.fanox.com Rev. 07 132/1388.8. CommissioningIt is recommended that the following safety measures are taken before starting up the facilityfor the first time, or after a trip event:• FANOX recommends the use of the KITCOM accessory with a battery in the front port. Thisadditional energy source allows the relay to be monitored and the trip to function without theneed for self-power in any breakdown situation.• Once all of the connections have been made, we recommend a check to make sure thatthey are correct, safe and well attached.• The “complete test” menu procedure should be applied. NOTE! See 5.7.• It is important to check that the measurements are correct once the facility has beenpowered up.Maintenance: FANOX recommends a minimum of one facility inspection per year, to at leastgo through the test menu and check the values of the measurements.9. APPENDIX9.1. IdentificationDate:………….....................…………………………………………………………………Manager:…….............………………………………………………………………………..Substation:…………………………………………………………………………………….Circuit:……………………………………………………………………………………........Model……………………………………………………………………………....................Serial no.........…………………………………………………………………………………Software Versions:........………………………………………………………………………9.2. ChecksCabling check: Box earth: Vaux value: 9.3. Test menuLEDs: Output 3 Output 1: Trip Output Output 2: