www.fanox.com Rev. 07 61/1385.11. CommandsBy HMI or by communications, depending on model is possible to:• Open Breaker• Close Breaker• Reset Thermal ImageWhen Open Breaker command is performed, the trip output is activated (originating thecorresponding event) and the message “trip general” will be displayed on main screen.5.12. Test MenuThe SIA-B relay has a test menu that can be used to check the operation of the signalingcomponents and the outputs. It is important to point out that the operation of the outputs does notwork if the test is performed with the commissioning battery.Press ◄,▼,► sequentially and hold OK until the “Test menu” appears on the display. The relay willask for the password “5555” to be entered in the test menu (or other if the customer password bydefault is “5555” has been modified).The test menu is accessed by pressing the “OK” key again, and the “▲” and “▼” keys can be usedto navigate through the different menu items. Each item can be activated or deactivated by pressing“OK” on it (if the item is deactivated, it is activated by pressing OK; if the item is activated, it isdeactivated by pressing “OK”). Press the “C” key to exit the test menu.Once the relay is in test menu mode all the LEDs will be activated simultaneously. In case of theoutputs, they will be activated or deactivated by pressing OK key:OUTPUT 1Deactivated Output 1 deactivatedActivated Output 1 activatedOUTPUT 2Deactivated Output 2 deactivatedActivated Output 2 activatedOUTPUT 3Deactivated Output 3 deactivatedActivated Output 3 activatedTRIP OUTPUTDeactivated Trip Output deactivatedActivated Trip Output activatedOnce each output is activated/deactivated the corresponding event will be recorded in the relay.NOTE: When performing the test menu, the protection will not be available, and it will be possible toopen the circuit breaker. Only authorized personnel can do this job.To obtain more detailed information, the method for navigating the menus is explained graphicallyin the keypad and display section.