GE Multilin239 Motor Protection Relay6-116 239PC SOFTWARE 6 239PC SOFTWARE6The program will now prepare the relay to receive the new firmware file. The 239 will display theUPLOAD MODE message. If the 239 has boot code revision 2.00 or earlier and a liquid crystaldisplay, the UPLOAD MESSAGE may not appear. Also, if the 239 has boot code revision 3.00 orlater and a vacuum fluorescent display, the UPLOAD MESSAGE may not appear. In both cases,the display returns to normal after the firmware upload has successfully completed.7. A dialog box will appear indicating the file transfer progress and time elapsed. The entire down-load process takes approximately three minutes.8. The following dialog box will appear when the firmware has been successfully loaded into therelay.9. Carefully read any notes indicated in the box and click on OK to return to the main screen. If therelay does not communicate with the 239PC program, ensure the following setpoints agree withthe 239PC settings shown in the COMMUNICATION/COMPUTER window.c) STEP 3—LOADING SAVED SETPOINTS1. Select Open from the File menu.2. Select the file containing the setpoints to be loaded into the relay (saved in Step 1).3. Select Properties from the File menu. The following dialog box will appear:4. Change the Version and Options to match the firmware version and options of the 239 relay. Therelay firmware and options can be in $352'8&7,1)2),50:$5(9(56,216 and $352'8&7,1)2