7-20239 Motor Protection RelayGE Multilin7 COMMUNICATIONS 7 COMMUNICATIONS7100D Reserved100E Reserved100F Reserved1010 RS485SERIALPORTSerial Communication Failure Alarm 0-1 1 --- F20 0 = OFF1011 Modbus Baud Rate 0-4 1 --- F13 3 = 96001012 Parity 0-2 1 --- F35 0 = NONE1013 Reserved1014 Reserved1015 Reserved1016 Reserved1017 Reserved1018 DEFAULTS Load Factory Defaults 0-1 1 --- F14 0 = NO1019 Clear Pre-trip Data 0-1 1 --- F14 0 = NO101A Clear Statistics Data 0-1 1 F14 0 = NO101B Reserved101C Reserved101D Reserved101E Reserved101F Reserved1020 CTINPUTSPhase CT Primary 0-1500 5 A F1 * 0 = OFF1021 Ground Sensing 0-3 1 --- F15 0 = OFF1022 Ground CT Primary 5-1500 5 A F1 1001023 Nominal Frequency 50-60 10 Hz F1 601024 Reserved1025 Reserved1026 Reserved1027 Reserved1028 MOTORDATAMotor Full Load Current 0-1500 1 *** F1 * 0 = OFF1029 Overload Pickup Inhibit 100-500 5 0.01xFLC F1 100 = 1.00102A Locked Rotor Current 5-110 1 0.1 xFLC F1 60 = 6.0 xFLC102B Safe Stall Time Cold 10-6000 1 0.1 x s F1 100 = 10.0 s102C Hot / Cold Curve Ratio 5-100 1 % F1 85%102D Disable Starts 0-1 1 --- F14 0 = NO102E Use Overload Pickup Inhibit On 0-2 1 --- F43 0 = RUN102F Reserved1030 ReservedTable 7–1: 239 MEMORY MAP (Sheet 8 of 18)REGADDR(HEX)GROUP DESCRIPTION REGISTERVALUERANGESTEPVALUEUNITS &SCALEFOR-MATFACTORYDEFAULT VALUE(CONVERTED)1, 2, 3, * , ** , *** , **** , †, ‡ See page 7–30 for explanation of Table notes.