CGCOMMUNICATIONS GUIDE MEMORY MAP369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG63141A Starter Aux Contact Type 0 1 1 - F109 0141B Starter Operation Monitor Delay Time 0 60 1 seconds F1 0 (Off)141C Starter Operation Monitor Type 0 2 1 - F115 0 (Off)141D Starter Operation Monitor Relays 0 15 1 - F169 0 (None)... ReservedOUTPUT RELAY SETUP1500 Trip Relay Reset Mode 0 2 1 - F117 01501 Alarm Relay Reset Mode 0 2 1 - F117 01502 Aux 1 Relay Reset Mode 0 2 1 - F117 01503 Aux 2 Relay Reset Mode 0 2 1 - F117 01504 Trip Relay Operation 0 1 1 - F161 01505 Alarm Relay Operation 0 1 1 - F161 11506 Aux1 Relay Operation 0 1 1 - F161 11507 Aux2 Relay Operation 0 1 1 - F161 0... ReservedFORCE OUTPUT RELAYS1510 Assign Communications Force Relays 0 15 1 N/A F169 01511 Trip Communications Force Relay OutputType 0 1 1 - F181 01512 Trip Pulsed Output Dwell Time 5 50000 1 100 ms F2 51513 Alarm Communications Force RelayOutput Type 0 1 1 - F181 01514 Alarm Pulsed Output Dwell Time 5 50000 1 100 ms F2 51515 Aux1 Communications Force RelayOutput Type 0 1 1 - F181 01516 Aux1 Pulsed Output Dwell Time 5 50000 1 100 ms F2 51517 Aux2 Communications Force RelayOutput Type 0 1 1 - F181 01518 Aux2 Pulsed Output Dwell Time 5 50000 1 100 ms F2 5... ReservedPROTECTION FUNCTION BLOCKING1520 Log Blocking Events 0 1 1 N/A F30 01521 Block Undercurrent/Underpower 0 1 1 N/A F30 01522 Block Current Unbalance 0 1 1 N/A F30 01523 Block Incomplete Sequence 0 1 1 N/A F30 01524 Block Thermal Model 0 1 1 N/A F30 01525 Block Short Circuit and Backup 0 1 1 N/A F30 01526 Block Overload Alarm 0 1 1 N/A F30 01527 Block Ground Fault 0 1 1 N/A F30 01528 Block Starts Per Hour and Time BetweenStarts 0 1 1 N/A F30 0... ReservedTHERMAL MODEL (0 = Off)1581 Overload Pickup Level 101 125 1 0.01xFLA F3 1011582 Assign Thermal Capacity Trip Relay 0 7 1 - F111 11583 Unbalance k Factor (0=Learned) 0 29 1 - F1 01584 Running Cool Time Constant 1 500 1 min F1 151585 Stopped Cool Time Constant 1 500 1 min F1 301586 Hot/Cold Safe Stall Ratio 1 100 1 - F3 1001587 RTD Biasing 0 1 1 - F103 01588 RTD Bias Minimum 0 198 1 °C F1 401589 RTD Bias Mid Point 0 199 1 °C F1 120158A RTD Bias Maximum 0 200 1 °C F1 155158B Thermal Capacity Alarm 0 2 1 - F115 0158C Assign Thermal Capacity Alarm Relays 0 7 1 - F113 1158D Thermal Capacity Alarm Level 1 100 1 % used F1 75158E Thermal Capacity Alarm Events 0 1 1 - F103 0158F Enable Learned Cool Time 0 1 1 - F103 01590 Enable Unbalance Biasing 0 1 1 - F103 01591 Motor Load Averaging Interval 3 60 3 cycles F1 3... ReservedTable CG–10: MEMORY MAP (Sheet 18 of 57)ADDR(hex)DESCRIPTION MIN. MAX. STEPVALUEUNITS FORMATCODEFACTORYDEFAULT