O-04 Control Word Timeout FunctionSelect the time-out function. The time-out function activates when the control word fails to be updated within the time period specified in par. O-03 ControlWord Timeout Time.Option: Function:[0] * Off Resumes control via serial bus (Network or standard) using the most recent control word.[1] Freeze output Freezes output frequency until communication resumes.[2] Stop Stops with auto restart when communication resumes.[3] Jogging Runs the motor at JOG frequency until communication resumes.[4] Max. speed Runs the motor at maximum frequency until communication resumes.[5] Stop and trip Stops the motor, then resets the frequency converter in order to restart: via the network, via the resetbutton on the Keypad or via a digital input.[7] Select setup 1 Changes the set-up upon reestablishment of communication following a control word time-out. If com-munication resumes causing the time-out situation to disappear, par. O-05 End-of-Timeout Function de-fines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the time-out function.[8] Select setup 2 See [7] Select setup 1[9] Select setup 3 See [7] Select setup 1[10] Select setup 4 See [7] Select setup 1NB!The following configuration is required in order to change the set-up after a time-out:Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.O-05 End-of-Timeout FunctionOption: Function:Select the action after receiving a valid control word following a time-out. This parameter is active onlywhen par. O-04 Control Word Timeout Function is set to [Set-up 1-4].[0] Hold set-up Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, untilpar. O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.[1] * Resume set-up Resumes the set-up active prior to the time-out.O-06 Reset Control Word TimeoutThis parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.Option: Function:[0] * Do not reset Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-out.[1] Do reset Returns the frequency converter to the original set-up following a control word time-out. The frequencyconverter performs the reset and then immediately reverts to the Do not reset [0] settingModbus TCP346