5-74 B90 Low Impedance Bus Differential System GE Multilin5.4 FLEXLOGIC™ 5 SETTINGS5ELEMENTNon-volatile latchesLATCH 1 ONLATCH 1 OFFNon-volatile latch 1 is ON (Logic = 1)Non-volatile latch 1 is OFF (Logic = 0)LATCH 2 to 16 Same set of operands as shown for LATCH 1ELEMENT:Setting groupSETTING GROUP ACT 1SETTING GROUP ACT 2SETTING GROUP ACT 3SETTING GROUP ACT 4SETTING GROUP ACT 5SETTING GROUP ACT 6Setting group 1 is activeSetting group 2 is activeSetting group 3 is activeSetting group 4 is activeSetting group 5 is activeSetting group 6 is activeELEMENTTime overcurrentTOC 1 PKPTOC 1 DPOTOC 1 OPThe time overcurrent 1 element has picked upThe time overcurrent 1 element has dropped outThe time overcurrent 1 element has operatedTOC 2 to 24 Same set of operands as shown for TOC 1ELEMENTTrip busTRIP BUS 1 PKPTRIP BUS 1 OPAsserted when the trip bus 1 element picks upAsserted when the trip bus 1 element operatesTRIP BUS 2 to 6 Same set of operands as shown for TRIP BUS 1ELEMENT:UndervoltageUNDERVOLTAGE 1 PKPUNDERVOLTAGE 1 DPOUNDERVOLTAGE 1 OPThe undervoltage 1 element has picked upThe undervoltage 1 element has dropped outThe undervoltage 1 element has operatedUNDERVOLTAGE 2 to 12 Same set of operands as shown for UNDERVOLTAGE 1 aboveFIXED OPERANDS Off Logic = 0. Does nothing and may be used as a delimiter in an equation list;used as ‘Disable’ by other featuresOn Logic = 1. Can be used as a test settingINPUTS/OUTPUTS:Contact inputsCont Ip 1 OnCont Ip 2 On↓Cont Ip 1 OffCont Ip 2 Off↓Cont Ip 96 OnCont Ip 96 Off(will not appear unless ordered)(will not appear unless ordered)↓(will not appear unless ordered)(will not appear unless ordered)↓(will not appear unless ordered)(will not appear unless ordered)INPUTS/OUTPUTS:Contact outputs,current(from detector onform-A output only)Cont Op 1 IOnCont Op 2 IOn↓(will not appear unless ordered)(will not appear unless ordered)↓INPUTS/OUTPUTS:Contact outputs,voltage(from detector onform-A output only)Cont Op 1 VOnCont Op 2 VOn↓(will not appear unless ordered)(will not appear unless ordered)↓Cont Op 1 VOffCont Op 2 VOff↓(will not appear unless ordered)(will not appear unless ordered)↓INPUTS/OUTPUTSDirect inputsDIRECT INPUT 1 On↓DIRECT INPUT 96 OnFlag is set, logic=1↓Flag is set, logic=1INPUTS/OUTPUTS:Remote double-point status inputsRemDPS Ip 1 BADRemDPS Ip 1 INTERMRemDPS Ip 1 OFFRemDPS Ip 1 ONAsserted while the remote double-point status input is in the bad stateAsserted while the remote double-point status input is in the intermediatestateAsserted while the remote double-point status input is offAsserted while the remote double-point status input is onREMDPS Ip 2 to 5 Same set of operands as per REMDPS 1 aboveINPUTS/OUTPUTS:Remote inputsREMOTE INPUT 1 OnREMOTE INPUT 2 OnREMOTE INPUT 3 On↓REMOTE INPUT 32 OnFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1↓Flag is set, logic=1INPUTS/OUTPUTS:Virtual inputsVirt Ip 1 OnVirt Ip 2 OnVirt Ip 3 On↓Virt Ip 64 OnFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1↓Flag is set, logic=1Table 5–7: B90 FLEXLOGIC™ OPERANDS (Sheet 2 of 4)OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION