5-188 D30 Line Distance Protection System GE Multilin5.7 CONTROL ELEMENTS 5 SETTINGS5Figure 5–99: TRIP BUS LOGIC5.7.3 SETTING GROUPSPATH: SETTINGS CONTROL ELEMENTS SETTINGS GROUPSThe setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPEDELEMENTS settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energizedLED) is in service. SETTING GROUPSSETTING GROUPSFUNCTION: DisabledRange: Disabled, EnabledMESSAGE SETTING GROUPS BLK:OffRange: FlexLogic operandMESSAGE GROUP 2 ACTIVATE ON:OffRange: FlexLogic operandMESSAGE GROUP 3 ACTIVATE ON:OffRange: FlexLogic operand↓MESSAGE GROUP 6 ACTIVATE ON:OffRange: FlexLogic operandMESSAGE GROUP 1 NAME: Range: up to 16 alphanumeric charactersMESSAGE GROUP 2 NAME: Range: up to 16 alphanumeric characters↓MESSAGE GROUP 6 NAME: Range: up to 16 alphanumeric charactersMESSAGE SETTING GROUPEVENTS: DisabledRange: Disabled, Enabled* * *SETTINGS= OffTRIP BUS 1 INPUT 2= OffTRIP BUS 1 INPUT 1= OffTRIP BUS 1 INPUT 16ORSETTINGS= EnabledTRIP BUS 1FUNCTION= OffTRIP BUS 1 BLOCK ANDANDLatchSRNon-volatile,set-dominantSETTINGS= EnabledTRIP BUS 1LATCHING= OffTRIP BUS 1 RESETFLEXLOGIC OPERANDTRIP BUS 1 PKPORSETTINGSTRIP BUS 1 PICKUPDELAYTRIP BUS 1 RESETDELAYTPKPT RSTFLEXLOGIC OPERANDRESET OPFLEXLOGIC OPERANDTRIP BUS 1 OP842023A1.CDR