6-22 D30 Line Distance Protection System GE Multilin6.4 RECORDS 6 ACTUAL VALUES66.4.3 OSCILLOGRAPHYPATH: ACTUAL VALUES RECORDS OSCILLOGRAPHYThis menu allows the user to view the number of triggers involved and number of oscillography traces available. TheCYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-raphy section of chapter 5 for additional details.A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. Refer to the COMMANDS CLEAR RECORDS menu for information on clearing the oscillography records.6.4.4 BREAKER MAINTENANCEPATH: ACTUAL VALUES RECORDS MAINTENANCE BREAKER 1(2)There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA 2 -cycles. Refer to theCOMMANDS CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME isdefined as the slowest operating time of breaker poles that were initiated to open. OSCILLOGRAPHYFORCE TRIGGER?NoRange: No, YesMESSAGE NUMBER OF TRIGGERS:0MESSAGE AVAILABLE RECORDS:0MESSAGE CYCLES PER RECORD:0.0MESSAGE LAST CLEARED DATE:2000/07/14 15:40:16 BREAKER 1BKR 1 ARCING AMP φA:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φB:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φC:0.00 kA2-cycMESSAGE BKR 1 OPERATING TIMEφA: 0 msMESSAGE BKR 1 OPERATING TIMEφB: 0 msMESSAGE BKR 1 OPERATING TIMEφC: 0 msMESSAGE BKR 1 OPERATINGTIME: 0 ms