GE Multilin D60 Line Distance Protection System 5-2535 SETTINGS 5.7 CONTROL ELEMENTS5The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole andthree pole modes, in one or two breaker arrangements. The autoreclose scheme provides four programs with differentoperating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing attempts.The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time delays.MESSAGE AR 3-P DEAD TIME 4:4.00 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR EXTEND DEAD T 1:OffRange: FlexLogic operandMESSAGE AR DEAD TIME 1EXTENSION: 0.50 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR RESET:OffRange: FlexLogic operandMESSAGE AR RESET TIME:60.00 sRange: 0 to 655.35 s in steps of 0.01MESSAGE AR BKR CLOSED:OffRange: FlexLogic operandMESSAGE AR BLOCK:OffRange: FlexLogic operandMESSAGE AR PAUSE:OffRange: FlexLogic operandMESSAGE AR INCOMPLETE SEQTIME: 5.00 sRange: 0 to 655.35 s in steps of 0.01MESSAGE AR BLOCK BKR2:OffRange: FlexLogic operandMESSAGE AR CLOSE TIME BKR2:0.10 sRange: 0.00 to 655.35 s in steps of 0.01MESSAGE AR TRANSFER 1 TO 2:NoRange: Yes, NoMESSAGE AR TRANSFER 2 TO 1:NoRange: Yes, NoMESSAGE AR BKR1 FAIL OPTION:ContinueRange: Continue, LockoutMESSAGE AR BKR2 FAIL OPTION:ContinueRange: Continue, LockoutMESSAGE AR 1-P DEAD TIME:1.00 sRange: 0 to 655.35 s in steps of 0.01MESSAGE AR BKR SEQUENCE:1-2Range: 1, 2, 1&2, 1–2, 2–1MESSAGE AR TRANSFER TIME:4.00 sRange: 0 to 655.35 s in steps of 0.01MESSAGE AR BUS FLT INIT:OffRange: FlexLogic operandMESSAGE AR EVENT:DisabledRange: Enabled, Disabled