GE Multilin D60 Line Distance Protection System 5-3215 SETTINGS 5.8 INPUTS AND OUTPUTS55.8.6 REMOTE INPUTSPATH: SETTINGS INPUTS/OUTPUTS REMOTE INPUTS REMOTE INPUT 1(32)Remote Inputs that create FlexLogic operands at the receiving relay are extracted from GSSE/GOOSE messages originat-ing in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function ofUserSt inputs is defined by the user selection of the FlexLogic operand whose state is represented in the GSSE/GOOSEmessage. A user must program a DNA point from the appropriate FlexLogic operand.Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for localuse. This programming is performed via the three settings shown above.The REMOTE INPUT 1 ID setting allows the user to assign descriptive text to the remote input. The REMOTE IN 1 DEVICE settingselects the remote device which originates the required signal, as previously assigned to the remote device via the settingREMOTE DEVICE (16) ID (see the Remote devices section). The REMOTE IN 1 ITEM setting selects the specific bits of theGSSE/GOOSE message required.The REMOTE IN 1 DEFAULT STATE setting selects the logic state for this point if the local relay has just completed startup orthe remote device sending the point is declared to be non-communicating. The following choices are available:• Setting REMOTE IN 1 DEFAULT STATE to “On” value defaults the input to logic 1.• Setting REMOTE IN 1 DEFAULT STATE to “Off” value defaults the input to logic 0.• Setting REMOTE IN 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest state isnot known, such as after relay power-up but before the first communication exchange, the input will default to logic 1.When communication resumes, the input becomes fully operational.• Setting REMOTE IN 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest state isnot known, such as after relay power-up but before the first communication exchange, the input will default to logic 0.When communication resumes, the input becomes fully operational.For additional information on GSSE/GOOOSE messaging, refer to the Remote Devices section in this chapter. REMOTE INPUT 1REMOTE INPUT 1 ID:Remote Ip 1Range: up to 12 alphanumeric charactersMESSAGE REMOTE IN 1 DEVICE:Remote Device 1Range: Remote Device 1 to Remote device 16MESSAGE REMOTE IN 1 ITEM:NoneRange: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,Config Item 1 to Config Item 32MESSAGE REMOTE IN 1 DEFAULTSTATE: OffRange: On, Off, Latest/On, Latest/OffMESSAGE REMOTE IN 1EVENTS: DisabledRange: Disabled, EnabledNOTE