4-2 D60 Line Distance Protection System GE Multilin4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES4RRTD Baud RateIP AddressIP Subnet MaskGateway IP AddressEthernet Sub Module Serial NumberNetwork Address NSAPIEC61850 Config GOOSE ConfRevWhen a settings file is loaded to a D60 that is in-service, the following sequence occurs:1. The D60 takes itself out of service.2. The D60 issues a UNIT NOT PROGRAMMED major self-test error.3. The D60 closes the critical fail contact.c) CREATING AND EDITING FLEXLOGICYou create or edit a FlexLogic equation in order to customize the relay. You can subsequently view the automatically gener-ated logic diagram.d) VIEWING ACTUAL VALUESYou can view real-time relay data such as input/output status and measured parameters.e) VIEWING TRIGGERED EVENTSWhile the interface is in either online or offline mode, you can view and analyze data generated by triggered specifiedparameters, via one of the following:• Event recorderThe event recorder captures contextual data associated with the last 1024 events, listed in chronological order frommost recent to oldest.• OscillographyThe oscillography waveform traces and digital states are used to provide a visual display of power system and relayoperation data captured during specific triggered events.f) FILE SUPPORT• Execution: Any EnerVista UR Setup file that is opened launches the application or provides focus to the alreadyopened application. If the file was a settings file (has a URS extension) that had been removed from the Settings Listtree menu, it is added back to the Settings List tree menu.• Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop targetfor device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and anyWindows Explorer directory folder are each mutually a file drag source and drop target.New files that are dropped into the Settings List window are added to the tree, which is automatically sorted alphabeti-cally with respect to settings file names. Files or individual menu items that are dropped in the selected device menu inthe Site List window are automatically sent to the online communicating device.g) FIRMWARE UPGRADESThe firmware of a D60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (that is, defaultvalues, minimum/maximum values, data type, and item size) can change slightly from version to version of firm-ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable, self-testmessage intended to inform users that the Modbus addresses have changed with the upgraded firmware. Thismessage does not signal any problems when appearing after firmware upgrades.NOTE