Page 20Segment 4 â On if Fail To Communicate report enabled.ã On if Log Full report enabled.ä On if Autotest report enabled.å On if Start/End programming report enabled.æ On if End Download report enabled.ç On if Sensor Low Battery report enabled.è On if Sensor Missing report enabled.é Reserved.Segment 5 â On enable Lost Clock service light.ã On enables Zone Doubling for zones 7 -12 (requires NX-200 Zone Doubling Kit).ä On disables on-board zones.å On will allow two trips on same cross-zone to activate an alarm.æ On will not allow zones that are force armed to report bypass.ç Reservedè Use internal crystal for clock.é Disable Temporal Siren on Fire. (Note: Must not be disabled for UL listed systems.)Refer to the feature definitions beginning on page 3.LOCATION 38 SWINGER SHUTDOWN COUNTLocation 38 contains the number of trips on a zone before that zone is bypassed automatically. Refer to the featuredefinitions beginning on page 3. Factory default is 1.LOCATION 39 KEYPAD SOUNDER CONTROL 1 segment, feature selectionâ On if keypad sounds for ATelephone Line Cut@ when the system is armed.ã On if keypad sounds for ATelephone Line Cut@ when disarmed.ä On if keypad sounds upon AC Power Failure.å On if keypad sounds when a Low Battery is detected.æ On if keypad sounds during Cross Zone trip time.ç On if keypad sounds for zone and box tampers.è Reserved.é On if keypad sounds for expander trouble (required for UL installations).LOCATION 40 SYSTEM TIMERS 10 segments, numerical dataLocation 40 contains the duration of various system timing functions. Example: If you desire the duration of theDynamic Battery Test to be 30 minutes, you should program [3]-[0]-[r] in segment 1 of this location. The [3]-[0] is thenumber of minutes, and the [r] stores the data and moves to the next segment of this location.SEGMENT DESCRIPTION SELECTIONS DEFAULT NOTES1 Dynamic Battery Testduration0 - 255 minutes 0 "0" = no testThe "Dynamic Battery Test" feature cannotexceed 4 hours for UL residential fireinstallations.2 AC Fail report delay 0 - 255 minutes 5 0 = no delay3 Power Up delay 0 - 60 seconds 60 0 = no delay4 Siren time 1 - 254 minutes 85 Telephone Line Cut delay 0 - 255 seconds 0 0 = no TLM6 Cross Zone time 0 - 255 minutes 5 0 = no Cross Zoning7 Chime time in 50 mS(1/20th second) increments0 - 255 mS 3 255 mS = 12 seconds0 follows zone, 255 is latched8 Dial delay 15 - 255 seconds 30 The "Dial Delay" feature shall be set to –0- forUL Listed systems. Must be disabled by zonetype in Loc 110-169.The combined Dial Delay and Entry Delay (loc24) must not exceed 1 minute fro SIA CP-01requirements.9 Fire Alarm Verification time 120 - 255seconds0 0= no Fire Alarm VerificationThis feature is not approved for residentialuse in California.10 Listen-In time 0 - 255 seconds 0 0 = no Listen-In timeThe "Listen-In" feature cannot be enabled forUL Listed systems.