g GEOPM_SGS_USM_10K_40K_0US_V010.doc 53/88 Operating Manual SG Series 10, 20, 30 & 40 kVA7.3 PROCEDURES FOR PARALLEL SYSTEM7.3.1 Parallel System start-upVerify on all Units, with open front door: Switches Q1 and Q2 must be open (Pos. O).1. Connect the Utility power on all UPS’s.(In case of separate inputs for Rectifier and Bypass, connect both).• Power supply starts up. Indicated with flashing alarm and buzzer sounds.• LED’s as indicated will be lit.• Press mute, to reset alarm and buzzer.First operated unit All other units of the system2. Close Q1 (Pos. I) on all Units.• When closing Q1 on the last unit of the parallel system, the Bypass of all Unitsconnects to the Load.• Rectifiers start automatically, blinking LED indicates Soft-start.• At the end of Rectifier Soft-start, the LED remains lit.• LED’s service check turn OFF.First operated unit All other units of the system3. Connect the Battery to all Units by closing the external Battery Switches orFuses, in case of External Battery.Continue ►