Critical PowerModifications reserved Page 51/91GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx User Manual TLE Series 160 - 500 UL S2BModule shutdownModule shutdownLoad Off command for a single UPS.NOTE !This command will immediately disconnect the Load.“Module shutdown” cannot disconnect the UPS from the Load with “Q2 -Manual Bypass switch” (only if provided by customer) closed.For the RPA Parallel SystemIn an RPA Parallel System, the “Module shutdown” command disconnects theLoad to the selected unit only (“Q1 – UPS Output switch” closed).Module shutdown RESET“Module shutdown” restore command for an individual UPS.Led Module shutdown statusShows the “Module shutdown” status: ACTIVE / NOT ACTIVESystem shutdownSystem shutdownLoad Off command for an RPA Parallel System.NOTE !This command will immediately disconnect the Load.“System shutdown” cannot disconnect the RPA Parallel System from theLoad with “Q2 - Manual Bypass switch” (only if provided by customer) closed.For the RPA Parallel SystemIf “System shutdown” is pressed on one unit connected to the Parallel Bus (“Q1 –UPS Output switch” closed), all the units are separated from the Load.System shutdown RESET“System shutdown” restore command for a RPA Parallel System.For the RPA Parallel SystemThe “System shutdown reset” must be done only on one unit connected to theParallel Bus (“Q1 – UPS Output switch” closed).Led System shutdown statusShows the “System shutdown” status: ACTIVE / NOT ACTIVEBoosterOnly for GE Service Center.