Critical PowerModifications reserved Page 67/91GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx User Manual TLE Series 160 - 500 UL S2BBATTERYCapacity Ah capacity of the Battery.Recharge Mode Recharge type of the Battery- Normal Valve Regulated Lead Acid Battery (VRLA), NiCdwithout boost-charge and Flooded Lead AcidBattery without boost-charge.- NiCd Nickel Cadmium Battery with boost-charge.- Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge.Float Voltage Voltage to maintain Battery Charging.Float voltage = Number of battery cells x battery float voltage per cell.Typical battery float voltage per cell (ask the battery manufacturer forconfirmation):Valve Regulated Lead Acid Battery (VRLA):2.27Vdc for cell240 cells x 2.27Vdc = 545VdcNiCd Battery without boost-charge:1.41Vdc for cell284÷309 cells x 1.41Vdc = 401 ÷ 436VdcNiCd Battery with boost-charge:1.41 (1.55 boost-charge) Vdc for cell281 cells x 1.41Vdc = 397 (436) VdcFlooded Lead Acid Battery without boost-charge:2.23Vdc for cell180÷195 cells x 2.23Vdc = 402 ÷ 435VdcFlooded Lead Acid Battery with boost-charge:2.23 (2.35 boost-charge) Vdc for cell180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) VdcRecharge Current Maximum Battery Recharge Current.Max 20% of battery capacity (Ah).Example: 100Ah – max. recharging current 20A.Stop Operation Time Residual Battery Autonomy time before UPS forced shut-down.Standard set 3 minutes.Settable from 1 minute to autonomy time in minutes.Cells Number of cells of the Battery, see “Float voltage”.Example: 240 battery cells- 40 blocks / 12Vdc Battery- 80 blocks / 6Vdc Battery- 240 blocks / 2Vdc BatteryNOTE !The values indicated above, must be considered as standard values.The actual programmed values must be the ones defined from the BatteryManufacturer.Continue →