5-32 T60 Transformer Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5The MMXU deadband settings represent the deadband values used to determine when the update the MMXU “mag” and“cVal” values from the associated “instmag” and “instcVal” values. The “mag” and “cVal” values are used for the IEC 61850buffered and unbuffered reports. These settings correspond to the associated “db” data items in the CF functional con-straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value “shall repre-sent the percentage of difference between the maximum and minimum in units of 0.001%”. Thus, it is important to know themaximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.The minimum value for all quantities is 0; the maximum values are as follows:• phase current: 46 × phase CT primary setting• neutral current: 46 × ground CT primary setting• voltage: 275 × VT ratio setting• power (real, reactive, and apparent): 46 × phase CT primary setting × 275 × VT ratio setting• frequency: 90 Hz• power factor: 2The GGIO1 status configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO1 STATUS CONFIGURATIONThe NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that areinstantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect untilthe T60 is restarted.The GGIO2 control configuration points are shown below:PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO2 CONTROL CONFIGURATION GGIO2 CF SPSCO 1(64)The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the T60virtual inputs. GGIO1 STATUS CONFIGURATIONNUMBER OF STATUSPOINTS IN GGIO1: 8Range: 8 to 128 in steps of 8MESSAGE GGIO1 INDICATION 1OffRange: FlexLogic™ operandMESSAGE GGIO1 INDICATION 2OffRange: FlexLogic™ operandMESSAGE GGIO1 INDICATION 3OffRange: FlexLogic™ operand↓MESSAGE GGIO1 INDICATION 128OffRange: FlexLogic™ operand GGIO2 CF SPCSO 1GGIO2 CF SPCSO 1CTLMODEL: 1Range: 0, 1, or 2