23IDS 805 Installer Manual 700-266-02H Issued September 2009Table 7: Output Options Default ValuesLoc. Event Value Default Action22 Alarm 2 Pulse prog. O/P 223 Audible priority 1 Pulse prog. O/P 124 Low battery 0 Disabled25 Auto test 0 Disabled26 Duress 1 Pulse prog. O/P 127 AC fail 0 Disabled28 Close 8 Set prog. O/P 3 High29 Open 13 Set prog. O/P 3 Low30 AC restore 0 Disabled31 Cancel 0 Disabled32 Fire 0 Disabled33 Medical 0 Disabled34 Strobe 0 Disabled35 Tamper 0 Disabled36 Silent priority 1 Pulse prog. O/P 137 Fire detector power 0 Disabled38 Chime 0 Disabled39 Communication fail 0 Disabled40 Phone No. 2 dialled 0 Disabled41 D/L complete 0 DisabledProgramming ExampleProgram output No. 2 to report open and close, with close HIGH and open LOW:It will be noted from Table 7 that output No. 2 is already assigned as the alarm output. This condition firstneeds to be disabled from output 2 before a new condition may be assigned otherwise CLOSE, OPENand ALARM will all be programmed to Programmable Output 2. To do this a [0] should be programmedinto location 22.The location for a close instruction is location 28. From Table 6 it will be noted that a value of [7]programmed into this location will cause output 2 to go high. This output will remain high until theappropriately programmed value gives the instruction for this output to be set low. It will be noted thatlocation 29 corresponds to an open condition. From Table 6 it will be noted that a value of [12] will driveoutput 2 low. Therefore, if a value of [12] is programmed into location 29 output 2 will be set low on anopen condition.If an output is programmed as a strobe output, the output will follow the sequence illustrated below.