20Table 1Setting of alarm parametersAfter choosing the group: alarm 1 configuration or alarm 2 configura-tion, it is possible to configure following alarm parameters (fig. 15):a) assignment of the alarm output parameter – kind of signal, onwhich the alarm acc. to the table 1 has to react,The set of the input quantity for alarms and analog outputs is included inthe table 1. The calculation way is shown in examples in the chapter 9.Value in reg-isters 4010,4015, 4020,4026Kind of quantityValue for percentage calcula-tion of alarms and outputvalues00 Lack of quantity /alarm or analogoutput switched off/ Lack01 Voltage of phase 1 Un [V] *02 Current in the wire of phase L1 In [A] *03 Active power of phase L1 Un x In x cos(0°) [W] *04 Reactive power of phase L1 Un x In x sin(90°) [var] *05 Apparent power of phase L1 Un x In [VA] *06 Coefficient of active power ofphase L1 107 Coefficient tgM of phase L1 108 Voltage of phase 2 Un [V] *09 Current in the wire of phase L2 In [A] *10 Active power of phase L2 Un x In x cos(0°) [W] *11 Reactive power of phase L2 Un x In x sin(90°) [var] *12 Apparent power of phase L2 Un x In [VA] *13 Coefficient of active power ofphase L2 114 Coefficient tgM of phase L2 115 Voltage of phase 3 Un [V] *16 Current in the wire of phase L3 In [A] *17 Active power of phase L3 Un x In x cos(0°) [W] *18 Reactive power of phase L3 Un x In x sin(90°) [var] *