4310. TECHNICAL DATAMeasuring Ranges and Admissible Basic ErrorsTable 10Measuredquantity Measuring range L1 L2 L3 6 BasicerrorCurrent 1/5A L1...L3 0.02...6 A~ z z z ±0.2%Voltage L-N 2.9...276 V~ z z z ±0.2%Voltage L-L 10... 480 V~ z z z ±0.5%Frequency 45.0...100.0 Hz z z z ±0.2%Active power -1.65 kW...1.4 W...1.65 kW z z z z ±0.5%Reactive power -1.65 kvar...1.4 var...1.65 kvar z z z z ±0.5%Apparent power 1.4 VA...1.65 kVA z z z z ±0.5%Tangens M -1.2...0...1.2 z z z z ±1%PF factor -1...0...1 z z z z ±0.5%Angle between Uand I -180o... 180 o z z z ±0.5%Input activeenergy 0...99 999 999.9 kWh z ±0.5%Developed activeenergy 0...99 999 999.9 kvarh z ±0.5%Reactive inductiveenergy 0...99 999 999.9 kWh z ±0.5%Reactive capaciti-ve energy 0...99 999 999.9 kvarh z ±0.5%Power Consumption:- in supply circuit x 6 VA- in voltage circuit x 0,05 VA- in current circuit x 0,05 VAAnalog Outputs: 2 programmable outputs:-20...0...+20 mA, R obc: 0..500 Waccuracy 0.2%Relay Outputs: 2 relays, voltageless NO contactsload capacity 250 V/ 0,5 A