Chapter 4 Block Reference©National Instruments Corporation4-13FieldPoint FP-3000 User ManualFP-3000 Specific ParametersCFG_OPTSAn option in the I/O function blocks to automatically set the scaling or alterthe block behavior. Generally, this option can make configuration easier.DEV_OPTSA list of device-wide options that can be turned on and off at will. Thecurrent firmware supports only one option.EXECUTION_STATISTICSA repository containing performance statistics for a given block. UseEXECUTION_STATISTICS to asses the performance of a givenconfiguration and allow appropriate changes to be made.Table 4-7. Configuration OptionsOption DescriptionAutomatically AdjustXD_SCALEEnabling this option allows the block toautomatically determine its XD_SCALEparameter, based on the physical I/O channelrange, which is set by parameters such asFP_AI_100 range.Ignore UnconnectedInterlock InputsBy default, all interlock inputs on the CDOblock must be good, or the block enters faultstate. Enabling this option allows inputs witha status of Bad::Not_Connected to beignored.Table 4-8. Device OptionsOptions DescriptionDisable CFG_OPTS in allI/O blocksThis bit disables all block configurationoptions in CFG_OPTS. It is notrecommended that this bit be set since theadditional behavior can make configurationeasier.