Appendix C Fieldbus ParametersFieldPoint FP-3000 User ManualC-4 ©National Instruments CorporationBLOCK_RESETLets you reset the statistics or the configuration of an individual functionblock.BYPASSAllows the normal control algorithm to be bypassed if the CONTROL_OPTparameter’s Bypass Enable option is selected. If control is bypassed, thePID uses its setpoint value as its output value and does not attempt to doany PID control.CHANNELUsed by I/O function blocks to select a physical I/O channel. This mappingis defined by the manufacturer. In the FP-3000, this parameter isautomatically updated when the FIELDPOINT_MODULE andFIELDPOINT_CHANNEL parameters are modified.CHECKBACKA list describing the state of the interlock logic in the CDO block. UseCHECKBACK to determine how interlocks are operating.Device NeedsMaintenance Now0x2000 The device needs to be maintained now.Power-Up 0x4000 The device has just powered up.Out of Service 0x8000 The block is currently out of service.Table C-2. Block Reset OptionsOption DescriptionContained Parameters Sets all the contained parameters (standard and FP-3000specific) of the function block to default values. This is usefulto set a specific block to a known state without affecting thebehavior of the other blocks in the FP-3000. The block shouldbe in OOS mode to reset the contained parameters.Statistics Resets the various statistics counts associated with the block.Table C-1. Error Codes (Continued)Error Code Code Description