68 SI-INTERBUS User GuideIssue Number: 112.6 Module error statusIf SI-Interbus detects an error during operation, it will force a trip in the drive, and writethe error code into this parameter.Table 12-3 Module error codes12.7 Background cycles per secondThis parameter displays the number of background cycles processed each second.Module Error StatusPr MM.050Default NoneType 8-bitAccess ROCode Fault Description0 No error detectedIndicates that the trip was not caused by the SI-Interbus. It ispossible to trip the drive externally via various communicationchannels.52 User control word trip The TRIP bit has been set in the control word.61 Configuration error An invalid configuration has been detected. Refer to Pr MM.049for configuration error codes.65 Network loss No new messages have been received for the specifiednetwork loss trip time.70 FLASH transfer error The SI-Interbus was unable to upload the configurationparameters from its FLASH memory to the drive.74 SI-InterbusovertemperatureIf the temperature inside the SI-Interbus exceeds 82 °C, theSI-Interbus will trip the drive.80 Inter-optioncommunication errorCommunications time-out has occurred, but SI-Interbus isunable to determine the reason for the error.81 Communication error toslot 1 Direct communications between SI-Interbus and anSI-Applications (or MCi2x0) in another slot has timed out.This can occur when the SI-Interbus has been mapped todirectly read or write the PLC (_P, _Q, _R, _S, _T, _U, _V, _W,_X or _Y) registers in an SI-Applications (or MCi2x0) and therelevant option module has been reset.82 Communication error toslot 283 Communication error toslot 398 Internal watchdog error Internal error. Cycle power to the drive to reset from this trip.If trip persists, replace the SI-Interbus.99 Internal software errorBackground Cycles Per SecondPr MM.052Default NoneType 8-bitAccess RO