41 AFP-3030 Operations Manual — P/N DOC-01-039:A 26/11/2015Read Status Smoke DetectorEnter an address to view its attributes (the cursor will be in the underlined section).NEXT POINT/PREVIOUS POINT - Press to view next or previous point.ACCEPT - Press to accept the displayed point for further viewing.Pressing the ACCEPT soft key on the Point Select Screen will display the information that corre-sponds to the chosen point. Each point type has its own screen.3.2 Smoke DetectorWhen a detector address is entered into the Point Select Screen and the ACCEPT soft key ispressed, the following screen will display if the detector is a smoke detector.Figure 3.2 Smoke Detector Screen - Read StatusDisplayLines 1- 4 - This could display any current event message, or, as in this example, the System Nor-mal message.Line 5 - This line contains the screen title and the address of the point being read.The area between the separator lines, lines 6-14, shows all information concerning the selectedpoint, which is N124L03D052 in the above example.Line 6 - Line 6 displays two statistics that display for inputs (detectors and modules) and zones; inthe above example they are:AUTOMATIC INACTIVEDAA Speaker CKT NxxxAyySn N indicates Node number, xxx = DVC/DVC-EM Node number, Aindicates DAA-5025 or DAA-5070 Audio Amplifier, yy = DAAaddress (01 through 32), S indicates Speaker circuit,n = Speaker circuit number (1-4).* The Nxxx preface to all the above address formats refers to the node number, where N = node, xxx = the network node number.Type Address Format*Table 3.1 Address Formats (2 of 2)NOTE: The first four lines of the display may indicate an alarm for a point unrelated to therequested point information displayed below them.L A K E V I E W G E N E R A L H O S P I T A LS Y S T E M N O R M A L1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1R E A D A D D R E S S : N 1 2 4 L 0 3 D 0 5 2A U T O M A T I C I N A C T I V EE L E V A T O R L O B B Y E A S T W I N GF I F T H F L O O R Z 0 0 5 S M O K E ( P H O T O )Z 0 0 5 , Z 0 2 7 , Z 0 6 6 , , ,, , , , ,V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R MA L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %A C T I O N / S T A T U S : N O N E / V E R Y C L E A NP E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 81 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1 B A C KP E A K S : 5 6 % C O U N T : 0 2 C O : 2 0 0 P P M T E M P : 1 0 0 o FFor FSC-851 detectors, the values appear in line14 above. Refer to More Information on page 11for explanation of fields.