45 AFP-3030 Operations Manual — P/N DOC-01-039:A 26/11/2015Read Status Monitor ModuleDisplayLines 1 through 14 - Refer to the descriptions in Section 3.2, “Smoke Detector”, on page 41.Line 15 - The current time and date are displayed in this line.Line 16 - Press B A C K to return to the previous screen.3.6 Monitor ModuleWhen a module address is entered into the Point Select Screen and the ACCEPT soft key is pressed,the following screen will display if the point is a monitor module.Figure 3.7 Monitor Module Screen - Read StatusDisplayLines 1 through 10 - Refer to the descriptions in Section 3.2, “Smoke Detector”, on page 41.Line 12 - When a Read Status is performed on an FMM-4-20 module, the current 4-20 mA sensor’sreading will be displayed in the units specified in point programming.Lines 13 and 14 - When a module is monitoring an AMPS-24, ACPS-610/E, or an ACPS-2406,information will appear in these lines in the following format.BATTERY VOLTAGE: 27.9 VOLTSCHARGER CURRENT: 0.0 AMPSLine 15 - The current time and date are displayed in this line.Line 16 - Press B A C K to return to the previous screen.L A K E V I E W G E N E R A L H O S P I T A LS Y S T E M N O R M A L1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1R E A D A D D R E S S : N 1 2 4 L 0 3 M 0 5 2A U T O M A T I C I N A C T I V EE L E V A T O R L O B B Y E A S T W I N GF I F T H F L O O R Z 0 0 5 P U L L S T A T I O NZ 0 2 2 , Z 0 2 7 , Z 0 6 6 , , ,, , , , ,1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1 B A C KBattery voltageand chargercurrent will appearin lines 13 and 14if the module ismonitoring anAMPS-24, ACPS-610/E, or anACPS-2406. Seetext below.Current 4-20mAsensor readingswill appear in line12. See text below.