CHANGE ALARM TIME PARAMETERThis section shows the programmings of several times, supplied by the control panel.Select the function from the menu by using CURSOR keys, and press ENTERThe programming is carried out as the previous one, except that it is possible to enetr different figures according to thetime you are programming.To enter the figures use CURSOR keys and press ENTER key to confirm.* Note 1 - ALARM CONTROL: to program a duration time equal to INFINITE, that is to say til the RESET, enter: 00-00» NOTE: the above list shows the control panel factory-default times.The same times are programmed in case of PROGRAMMING CLEARINGPROGRAMMING THE ALARM CONTROL MODULATIONThis function allows to modify the relay operating frequency of: ALARM, PREALARM and SOUNDERS, when activated.It is possible to achieve pause and activation times multiple of 1 second which may be programmed in cycles of 8 secondsrepetitive.SOUND EXAMPLES:Example Nr. 1= two 1-second beeps + one 3-second sound (repeated)Example Nr. 2= 2-second beep (repeated)Example Nr. 3= 3-second beep (repeated)If the sequence programming is carried out entering a value equal to 1, a steady sound will be obtained (this is the factory-default value).The following controls may be programmed:• PREALARM• ALARM• SOUNDERUse CURSOR keys to select the control, then press ENTER to modify it.Use CURSOR keys to program 0/1 values, then press ENTER to confirm the programming.The same as for the other functions, press ESC key to leave the function without changing the existing programming.CFP-600-Prog-4.VP Installation and Operating Manual Page 15Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIADEFAULT MIN MAX30 seconds 1 second 09-592 minutes 0 seconds 19-5930 seconds 0 seconds 19-5920 minutes 20 minutes 99-59• Prealarm Time (Day mode)• Alarm Time (* Note 1)• Sounder Control Activation Time• Walk-Test and Line test max Time0 1 0 1 0 1 1 1 0 1 1 0 0 1 1 0 1 1 1 0 1 1 1 0ALARM MODULAT. |A08CONFIGURATION |G08|D00|E00ALARM MODULAT. |A08PREAL. SEQUENCE|G0811111111 |D00|E00