33 HEATING CAPACITY PERFORMANCE DATAModel PowerSourceInlet Air Outdoor Temperature (°C W. B.)(CS-) External Static Pressure (Pa) Entering Air -6 °C 0 °C 6 °C 12 °CAir Volume (m3/min) Dry Bulb (°C) H.C. IPT H.C. IPT H.C. IPT H.C. IPTA24BB4P 230V, 15 5.18 1.74 6.21 1.99 7.46 2.37 8.66 2.7950Hz, 17 20 4.90 1.84 5.86 2.12 7.10 2.49 8.52 2.89Single phase 25 4.62 1.94 5.54 2.24 6.75 2.61 8.17 2.95A28BB4P 230V, 15 5.84 1.92 7.00 2.19 8.40 2.60 9.76 3.0750Hz, 18 20 5.52 2.03 6.60 2.33 8.00 2.74 9.60 3.18Single phase 25 5.20 2.14 6.24 2.47 7.60 2.88 9.20 3.22A34BB4P 230V, 15 8.18 2.49 9.80 2.84 11.8 3.37 13.7 3.9850Hz, 27 20 7.73 2.63 9.24 3.02 11.2 3.55 13.4 4.12Single phase 25 7.28 2.77 8.74 3.20 10.6 3.73 12.9 4.30A34BB4P 400V, 15 8.18 2.38 9.80 2.72 11.8 3.23 13.7 3.8150Hz, 27 20 7.73 2.52 9.24 2.89 11.2 3.40 13.4 3.94Three phase 25 7.28 2.65 8.74 3.06 10.6 3.57 12.9 4.07A43BB4P 400V, 15 10.2 2.87 12.3 3.28 14.7 3.90 17.1 4.5950Hz, 30 20 9.66 3.03 11.6 3.49 14.0 4.10 16.8 5.00Three phase 25 9.10 3.20 10.9 3.69 13.3 4.31 16.1 5.60A50BB4P 400V, 15 11.3 3.48 13.6 3.98 16.3 4.72 18.9 5.5750Hz, 31 20 10.70 3.68 12.8 4.22 15.5 4.97 18.6 6.06Three phase 25 10.08 3.88 12.1 4.47 14.7 5.22 17.8 6.60Legend:H.C. = Heating CapacityIPT = Power ConsumptionModel Heating capacities are based on conditions below. Model Heating capacities are based on conditions below.CS-A24BB4P 1 phase, 50Hz, 230V CS-A28BB4P 1 phase, 50Hz, 230VHeating capacity Indoor temp. 20°C D.B. Heating capacity Indoor temp. 20°C D.B.7.1kW Outdoor temp. 7°C D.B. 6°C W.B. 8.0kW Outdoor temp. 7°C D.B. 6°C W.B.Standard air volume 17 m3/min Standard air volume 18 m3/minModel Heating capacities are based on conditions below. Model Heating capacities are based on conditions below.CS-A34BB4P 1 phase, 50Hz, 230V CS-A34BB4P 3 phase, 50Hz, 400VHeating capacity Indoor temp. 20°C D.B. Heating capacity Indoor temp. 20°C D.B.11.2kW Outdoor temp. 7°C D.B. 6°C W.B. 11.2kW Outdoor temp. 7°C D.B. 6°C W.B.Standard air volume 27 m3/min Standard air volume 27 m3/minModel Heating capacities are based on conditions below. Model Heating capacities are based on conditions below.CS-A43BB4P 3 phase, 50Hz, 400V CS-A50BB4P 3 phase, 50Hz, 400VHeating capacity Indoor temp. 20°C D.B. Heating capacity Indoor temp. 20°C D.B.14.0kW Outdoor temp. 7°C D.B. 6°C W.B. 15.5kW Outdoor temp. 7°C D.B. 6°C W.B.Standard air volume 30 m3/min Standard air volume 31 m3/min151CASSETTE TYPE