•• Remote control displays and indoor unit operation continue during this time.•• The 10 minutes countdown is cleared if the compressor stops or if the temperature at the outdoor unit outlet rises to 13.5°C orhigher.27.2. Drain pump control1. Basic operationDuring cooling mode, dry mode or defrost mode operation, the drain pump turns on when the compressor turns on. (The drainpump turns on during freezing prevention control.)•• When the compressor turns off, the drain pump will still continue its operation for 6 more minutes.•• If the drain pump is running when operation stops or when the operating mode is changed, the drain pump will still continueits operation for 6 more minutes.2. Drain water problemsa. StartingIf it is detected that the float switch is off, the drain pump turns on for 5 minutes. If the float switch is still found to be off afterthese 5 minutes have passed, or if the float switch is found to turn off twice during another 30 minutes period, a drain watererror will be generated.b. Normal operationAfter extension control (louvre initialization and pre-heating cancel), the indoor units and outdoor units stop running. LED2on the indoor unit self-diagnosi s LED panel will flash, and “CHECK” will appear on the wired remote control display.The error code (F15-01) can be displayed by pressing the CHECK button.When the wireless remote control is being used, the OPERATION indicator on the ray receiver will flash.94CASSETTE TYPE