Model Cooling capacities are based on conditions below.CS-A24BB4PCooling capacity6.3 kW1 phase, 50Hz, 230VIndoor temperature 27°C D.B. 19°C W.B.Outdoor temperature 35°C D.B.Standard air volume 17m3/minEntering Temperature Air Entering Condenser (°C D.B.)Air 25 30 35 40 43Temperature TC TC TC TC TCD.B. W.B. kW kW kW kW kW17 6.40 6.10 5.81 5.40 5.1127 19 6.94 6.62 6.30 5.86 5.5422 7.55 7.14 6.74 6.39 6.04Entering Temperature Air Entering Condenser (°C D.B.)Air 25 30 35 40 43Temperature IPT IPT IPT IPT IPTD.B. W.B. kW kW kW kW kW17 2.00 2.15 2.234 2.54 2.6427 19 2.13 2.30 2.50 2.72 2.8322 2.16 2.33 2.54 2.75 2.87Model Cooling capacities are based on conditions below.CS-A28BB4PCooling capacity7.1 kW1 phase, 50Hz, 230VIndoor temperature 27°C D.B. 19°C W.B.Outdoor temperature 35°C D.B.Standard air volume 18m3/minEntering Temperature Air Entering Condenser (°C D.B.)Air 25 30 35 40 43Temperature TC TC TC TC TCD.B. W.B. kW kW kW kW kW17 7.35 7.04 6.67 6.21 5.8127 19 7.82 7.53 7.10 6.60 6.1822 8.51 8.13 7.70 7.23 6.84Entering Temperature Air Entering Condenser (°C D.B.)Air 25 30 35 40 43Temperature IPT IPT IPT IPT IPTD.B. W.B. kW kW kW kW kW17 2.15 2.35 2.52 2.71 2.8327 19 2.29 2.47 2.69 2.85 3.0122 2.34 2.52 2.74 2.88 3.04TC = Total Cooling CapacityIPT = Power Consumption15.2. COOLING PERFORMANCE63CASSETTE TYPE