101o Heating mode Sleep operation will not undergo temperature shift when it collaborate with below operation. However, it willexecute the delay timer.o Powerful mode operationo Auto mode operationStop Condition: When sleep operation is cancel by pressing respective button until sleep timer reaches 0.0h. ON/OFF button is pressed.When sleep operation ends.14.13 HA Terminal (HAJEM-A) Enable digital connection from indoor unit to external devices. Control items:1 Start/stop input.2 Start/stop signal output. Condition1 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.(1 pulse signal: shortage status 200~300msec)2 3-4 (Static output): 5V output during the unit ON. No output at OFF.Example of wiring:Note: The wire length from indoor unit to the external interface must be within 1.9 meters. The wire must be doubleinsulation type and a ferrite core to be added to reduce noise. Proposed core spec is J0KE00000147 with HeatShrinkage Tube.The signal between indoor unit and the external interface must be isolated by photo-coupler of approval type (e.g:Semko, VDE etc).detavitcAremiTpeelSlamroNMax 9 HrsSet Temp1 Hr-1°CON/OFF input(Pin 1-2)Monitor output(Pin 1-2)ON ONOFFUnit condition200~300msec+5VMCUHAJEM-A(XH type)Indoor UnitPCB+5V1 1 1 1#A4 #A4#B4240 mmMax 1900 mm#A K1KA04AA0347 (Maker: JST; Maker code: B4B-XHTV4)#B Maker: JST; Maker code: XHP-4#B4Core4T