2.1 Analog Input Unit (FP0R-AD4/AD8)2-32.1.2 Setting of Mode Switch Setting of the mode switchItem No. SettingsResolutionand FP0-A21-compatible12-bit modeinput range1 OFF ON OFF ON2 OFF OFF ON ONFP0-A80-compatible12-bit mode0 to 5V/0 to 20mA(Note 1)FP0-A80-compatible12-bit mode-10 to +10VFP0-A80-compatible12-bit mode-100 to +100mV(Note 2)14-bit mode(Note 3)The numberof convertedCH3 OFF ON OFF ON4 OFF OFF ON ON2ch(CH0-CH1)4ch(CH0-CH3)6ch(CH0-CH5)8ch(CH0-CH7)Input averaging 5 OFF: Averaging Not performed, ON: Averaging Performed(Note 1): When the both switch No.1 and No.2 are OFF, the voltage/current is switched by the connection method.(Note 2): This has been implemented in version 1.2 or later. In version 1.1 or earlier, this is reserved for the system(not available).(Note 3): In the 14-bit mode, the input range is set by writing into the operation memory WY with a user program.(Note 4): All the switches are set to OFF at the factory.(Note 5): The switch settings will be valid when the power is turned ON from OFF. The settings will not change if theoperation power supply is switched when it is ON.