Analog Input Averaging Processing5-45.2 Setting of Averaging Processing5.2.1 Enabling Averaging ProcessingThe averaging processing can be set by the following methods. 12-bit FP0-A80 compatibility mode / FP0-A21 compatibility modeThe averaging processing is enabled only when the mode switch No.5 of the unit is ON.• The averaging method of all channels is the moving average 10 times (Max. and min.removal). 14-bit mode• The averaging processing is enabled only when the mode switch No.5 of the unit is ON.• The default is the moving average 10 times (Max. and min. removal).• It is possible to specify the averaging method (Moving average 10 times / No. of averagingtimes: 64 / No. of averaging times: 128 / No averaging) by a user program for each channel.REFERENCE• For details of the setting method of the mode switch, refer to the chapter 2“Names and Functions of Parts“.• For details of the programming method for the analog input unit (FP0R-AD4/AD8), refer to “4.2.2 Setting of Input Range and Averaging Processing(14-bit Mode Only)“.• For details of the programming method for the analog I/O unit (FP0R-A21/A42), refer to PAGEREF“4.4.5 Switching of Input Range and AveragingMethod (14-bit Mode Only)“.