7.2 Analog Output Unit7-57.2.2 Points of ReplacementThe points for replacing the conventional models FP0A04V or FP0A04I with the new modelFP0RDA4 as an alternative are described below. Hardware• Turn off the mode switch No.1 and select "12-bit FP0A04 compatibility mode". The voltageoutput range is "-10 to 10 V DC", and the current output range is "4 to 20 mA DC".• The new model FP0RDA4 has two terminal blocks for the voltage output and current output.They are connected according to the application.• In the case of FP0RDA4, select whether to output signals to the voltage output or currentoutput for each channel with the mode switch. The factory default setting is the voltageoutput for all channels. Change the mode switch setting as necessary.Item FP0A04V compatibility FP0A04I compatibilityAppearanceTerminal block The terminal block on the voltage outputside is used.The terminal block on the current outputside is used.Mode switchThe 12-bit FP0A04 compatibility mode isselected.The voltage output is selected for allchannels.The 12-bit FP0A04 compatibility mode isselected.The current output is selected for allchannels. SoftwareUser programs created for the conventional models FP0A04V and FP0A04I can be used asthey are.REFERENCE• For details of the setting method of the mode switch, refer to “2.2.2 Settingof Mode Switch“.