Creating Programs4-324.4.5 Switching of Input Range and Averaging Method (14-bit Mode Only)When selecting the 14-bit mode in the analog I/O unit (FP0R-A21/A42), the input range oraveraging method for each channel can be set by user programs. I/O allocation (External output WY)Y3FY3EY3DY3CY3BY3AY39Y38Y37Y36Y35Y34Y33Y32Y31Y30Y2FY2EY2DY2CY2BY2AY29Y28Y27Y26Y25Y24Y23Y22Y21Y20A1A0Output data of CH1 (14bit)Input average setting: CH0-CH3CH1 output range settingA1A0Output data of CH0 (14bit)Input average setting: CH0-CH3CH0 output range settingA1 A0 Item A1 A0 Item0 0 CH1 output data setting 0 0 CH0 output data setting0 1 Input average setting 0 1 Input range setting1 0 CH1 output range setting 1 0 CH0 output range setting1 1 CH1 output data setting 1 1 CH0 output data settingSet the contents allocated to CH0 to CH3 for the input averaging processing and input rangeby replacing the following 8-bit data with Hex data.Y3FY3EY3DY3CY3BY3AY39Y38Y37Y36Y35Y34Y33Y32Y31Y30Y2FY2EY2DY2CY2BY2AY29Y28Y27Y26Y25Y24Y23Y22Y21Y20A1A0CH3 CH2 CH1 CH0 A1A0CH3 CH2 CH1 CH0Specify 0 D1D0D1D0D1D0D1D0 Specify 0 D1D0D1D0D1D0D1D0D1 D0 Averaging (Common to each channel) D1 D0 Range (Common to each channel)0 0 Moving average 10 times (Max. andmin. removal) 0 0 -10V to +10V0 1 No. of averaging times: 64 0 1 -5V to +5V1 0 No. of averaging times: 128 1 0 0 to 10V1 1 No averaging 1 1 0 to 5V / 0 to 20mA Default settingsThe default settings are as follows; Input range for all channels: -10 to +10 V, Averaingprocessing: Moving average processing 10 times (Max. and min. removal). The averagingprocessing is enabled when the mode switch No. 5 is ON.